Voltage drop calculator: find the volts lost and percent drop on a copper or aluminum wire run by length, size and amps.

Editorial review: Farrow (pseudonym; identity and professional credentials are not disclosed). This page is for educational purposes, not professional advice.

Updated

Your inputs

A
ft
V

Results update as you type. Nothing you enter leaves your device.

Results

Voltage drop
4.97 V
Percent drop
4.14%
Voltage at load
115 V
Against 3% guideline
Over limit: use thicker wire

Example with the starting values

These results use the calculator's initial inputs. Change the values above to calculate your own estimate.

Inputs

Conductor
Copper
Phase
Single-phase
Wire size
10 AWG
Current
20 A
One-way length
100 ft
Source voltage
120 V

Results

Voltage drop
4.97 V
Percent drop
4.14%
Voltage at load
115 V
Against 3% guideline
Over limit: use thicker wire

How does the Voltage Drop Calculator work?

Voltage drop = multiplier x K x current x one-way length / circular mils. K is 12.9 for copper and 21.2 for aluminum. The multiplier is 2 for single-phase and 1.732 for three-phase.

The National Electrical Code recommends keeping branch-circuit drop to about 3% and the total to 5%.

Frequently asked questions

What is an acceptable voltage drop?

Under 3% on a branch circuit is the usual guideline, and 5% for feeder plus branch together.

How do I reduce voltage drop?

Use a thicker wire, shorten the run or raise the voltage.

Do I use one-way or round-trip length?

One-way. The formula's multiplier already counts the return path.

Why does 3-phase use 1.732?

It is the square root of 3, which reflects the phase relationship in a balanced three-phase circuit.